Some of the key requirements for fire doors that you should be aware of, are as follows:
In most cases, doors throughout the building should have a minimum of 30 minutes fire resistance, i.e. be FD30 rated, with consideration of compartmentalisation. For example, in domestic buildings above two levels, every door that leads to the stairwell must be a fire door. Where restricted smoke leakage is needed, the door will have a suffix (S) added, e.g. FD30S. Where the door is in a compartment wall separating buildings, it should be a minimum of 60 minutes fire resistance. For full details about which doors you should use and where in a building, including the differences between domestic and non-domestic premises, see table C1 in the two documents.
They should be classified in accordance with BS EN 13501-2, tested to the relevant European method from the following: BS EN 1634-1, 1634-2, 1634-3. This will prove that the manufacturer is supplying products that have been tested in accordance with BS EN 1631-1 and achieve the minimum performance specifications for safety, as set out in the Approved Documents.
They should be fitted with a self-closing device. This ensures that the door closes automatically from any angle, to minimise the spread of fire and smoke. Doors that you usually keep locked should release when the alarm sounds, and you should test this alongside alarms.
The essential components of fire door hinges should be made entirely from materials that have a minimum melting point of 800 °C. Note that, because of the weight of fire doors, they are typically installed with three hinges, though the current BS standards allow two hinges in some circumstances. It’s important to check any accompanying information to ensure that your fire door meets all the necessary requirements for safety.
They should be marked on both sides with a ‘Fire door keep shut’ sign, to comply with BS 5499-5. There are some variations depending on the type of door, e.g. if it should be kept locked when not in use, the sign can say ‘Fire door keep locked shut’.
Furthermore, to comply with safety standards and ensure fire doors prevent the spread of fire and smoke:
Fire doors must have appropriate intumescent seals. These are crucial, as they expand when exposed to heat and fill in the gaps between the door and the frame, preventing smoke and fire from travelling through. As the British Woodworking Federation (BWF) Fire Door Alliance states, the recommended seal size for most modern 30 minute doors is 15 mm X 4 mm. The recommended seal size for most modern 60 minute fire doors is 20 mm X 4 mm, or two No. 10 mm X 4 mm.
The gap between the door and the frame must not exceed 3mm – this is along the two sides and across top of the door leaf. The gap at the bottom of the door can usually be around 10 mm for non-smoke conditions, though it should be 3 mm when smoke seals are required.
Check for a label or plug that will be somewhere on the door. These indicate that the door is certificated and compliant with the necessary standards for safety. The labelling will usually identify the manufacturer and fire rating.
You should also check for certification labelling, which will indicate that the manufacturer is a member of an accredited and recognised third party certification body and that the fire door has been made in accordance with safety standards. The two commonly recognised certification bodies are the BWF Fire Door Alliance or BM TRADA. BM TRADA uses the Q-Mark, which are coloured plugs that indicate the rating of the door and other key information.